IRRS-02-0004
Gossen Metrawatt - AC Pro Type II Adapter
455,000.00 ฿
อแดปเตอร์สำหรับเชื่อมกับสถานีชาร์จรถยนต์ไฟฟ้า (AC TYPE II ADAPTER)
Single and 3-Phase Test Adapter for Testing for the Effectiveness of Protective Measures at Electrical Charging Stations with the Profitest Master,
Simulating Fictitiously Connected Electric Vehicles and Simulating the
Current-Carrying Capacity of Cord Sets per IEC 61851-1
• Vehicle Simulation (CP)
Vehicle states A through E are selected with a rotary switch.
• Cable Simulation (PP)
The various codings for charging cables with 13, 20, 32 and
63 A, as well as “no cable connected”, can be simulated with
the help of a rotary switch.
• Fault Simulation
Simulation of a short-circuit between CP and PE by means of
a rotary switch
• Indication of Phase Voltages via LEDs
Depending on the charging station, either one or three phases
can be active.
• Testing of electrical charging stations with permanently connected
charging cable due to extended CP test pin
• CP Socket for PWM signal evaluation
Technical Data | |
Vehicle Simulation (CP) | |
States A, B, C, D and E can be simulated in accordance with IEC 61851. The various vehicle states are selected by means of a rotary switch. | |
State A: | No vehicle connected |
State B: | Vehicle connected, but not ready for charging |
State C: | Vehicle connected and ready for charging without venting |
State D: | Vehicle connected and ready for charging with venting |
State E: | Error – short circuit between CP and PE via internal diode |
Cable Simulation (PP) | |
The various codings for charging cables with 13, 20, 32 and 63 A can be simulated. It’s also possible to simulate the “no cable” state. The various charging cables are simulated by connecting different resistances between PP and PE with the help of a rotary switch. The following values are possible in accordance with IEC 61851: | |
No cable: | 0 Ω |
13 A cable: | 1.5 kΩ |
20 A cable: | 680 Ω |
32 A cable: | 220 Ω |
63 A cable: | 100 Ω |
Connection Values | |
Input voltage | 400 V (3-phase) |
Frequency | 50 Hz |
Test consumer | |
power | max. 2.9 kVA (no continuous operation!) |
Electrical Safety | |
Protection class | II |
Test voltage | 3.5 kV AC |
Measuring category | CAT III 300 V |
Pollution degree | 2 |
Ambient Conditions | |
Operating temperature | –10 °C to +45 °C |
Storage temperature | –25 °C to +60 °C |
Relative humidity | Max. 80%, condensation is ruled out |